Model |
Functional Details |
Cabinet Style |
AVA11 |
VOLTAGE OPERATED AUXILIARY RELAY WITH SR CONTACTS |
CSB - 80 |
|
|
|
VOLTAGE OPERATED AUXILIARY RELAY WITH SR CONTACTS : AVA11
Standard Specifications :
Operating Limits: |
70 to 110% of rated coil voltage. |
Operational Time : |
20 - 25 ms at nominal rated voltage. |
Coil Rating : |
24V / 30V / 110V / 220V DC or AC. |
Burden |
@ 30 VDC / 24VDC : 3 VA, @110 VDC : 2 VA, @ 220VDC : 4 VA. |
Operational Indicator : |
Mechanical Flag (Red for Alarm, White for Normal) in window : HR Type. |
Contacts : |
4 Pair of SR. (Self Reset). |
Combinations : |
4 NO, 3NO + 1NC, 2NO + 2NC, 1NO + 3NC. (Ref. : Drawing AXL00501 ). |
Relay conforms : |
IS : 3231 -1981 Fully for all requirements. |