ADR213B – Single Pole Tx. Differential

ADR213B

Specifications

  • Specially designed for Traction OHE Protection. As per RDSO specs TI/SP/PSI/PROTCT/4050.
  • Dual Slop characteristic for excellent through fault stability.
  • Operation based on fundamental frequency value.
  • Harmonics Restrain for Tx charging and CT saturation condition.
  • Instantaneous Differential Current Protection.

Model Functional Details Cabinet Style
ADR213B Numerical Single Pole Tx. Differential Relay CSE-H-130
 



Numerical Single Pole Tx. Differential Relay : ADR213B

General Description

ADR213B second generation Numerical Transformer Protection Relay for Traction Application. It consist all the necessary protection and monitoring functions required for traction feeder.

  • Disturbance Recorder. 50 cycles of actual waveform of currents (45 pre-fault & 5 post fault) are captured & saved in the built-in memory with date time stamping, for analyzing fault.
  • Separate Communication Ports for SCADA (RS485) as well as Local testing (RS232C)
  • Fully communicable with IEC standard open protocol.
  • Very low burden on CT (less than 0.5VA).
  • Online display of Primary current i.e. load current and unbalance current.
  • Continuous monitoring of module’s internal hardware and alarm generation in case of failure of any critical components.
  • Large 20x4 LCD display for Parameter and setting display
  • Facility to synchronised Relay time with external GPS network.
  • 10 Digital Output contacts for local alarm as well as tele-signalling.
  • 9 Optically isolated digital status input for monitoring of status and avoid used of external relay logic.
  • 100 nos of event memory, event such CB close, Trip, digital status change, relay pkp etc. All events are with date and time stamped up to 1ms.